Modular UPS 800KVA
Online Double Conversion · 3 Phase In / 3 Phase Out.
Model: HQ-M800
Capacity
800 kVA
Efficiency
Up to 96% (ECO up to 99%)
Input voltage range (full load)
304–478 VAC
Battery (configurable)
30–44 units (default: 40 units)
| Parameter | Value |
|---|---|
| Model | HQ-M800 |
| Capacity | 800 kVA |
| Cabinet type | 14 Modules |
| Power module capacity | 60 kVA |
| Input wiring | 3 Phase + N + PE |
| Rated input voltage | 380/400/415 VAC (Line voltage) |
| Rated input frequency | 50/60 Hz |
| Input voltage range (full load) | 304–478 VAC |
| Input frequency range | 40–70 Hz |
| Input power factor | > 0.99 |
| THDi | < 3% (100% linear load) · < 5% (100% non-linear load) |
| Bypass rated voltage | 380/400/415 VAC (Line voltage) |
| Bypass voltage range | Default: -20% ~ +15%; configurable upper: +10%, +15%, +20%, +25%; lower: -10%, -15%, -20%, -30%, -40% |
| Battery voltage | ±240 VDC (±180 ~ ±264 VDC), 30–44 units configurable (default: 40 units) |
| Output rated voltage | 380/400/415 V (Line voltage) |
| Output rated frequency | 50/60 Hz |
| Output power factor | 1 |
| Voltage accuracy | ≤ ±1.0% (balanced) · ≤ ±5.0% (unbalanced) |
| Frequency accuracy | 50/60 Hz ± 0.1% |
| Frequency tracking range | ±0.5 Hz ~ ±5 Hz (default: ±3 Hz) |
| THDu | ≤ 2% (100% linear load) · ≤ 4% (nonlinear load) |
| Three-phase accuracy | 120° ± 1° |
| Crest factor | 3:1 |
| Overload | ≤105% long run; 105–110% 60 min; 110–125% 10 min; 125–150% 1 min; >150% switch to bypass immediately |
| Display | 10" Color touch screen + LED |
| Protection class | IP20 |
| Communication | RS232/RS485; optional: SNMP / dry contact |
| Noise | < 70 dB @ 1 m |
| Operating temperature | 0 ~ 40°C |
| Humidity | 0 ~ 95% (Non-condensing) |
| Altitude | <1000 m no derate; >1000 m derate 1% per 100 m |
| Standard | IEC62040-1-1; IEC62040-2; IEC62040-3 |
| System size (W×D×H) | 1800 × 850 × 2000 mm |
| Module size (W×D×H) | 440 × 720 × 130 mm (3U) |
| System weight | 610 kg |
| Module weight | 35 kg (60 kVA) |
| Minimum order | 60 |